Remote Communications & Overview Displays
DSE891 MKII
DSEWebNet® Gateway - Ethernet Only
DSEWebNet® software is accessed using an Internet browser or the dedicated app. Users are able to perform multiple tasks including: monitoring equipment, clearing alarm conditions, starting/stopping equipment and monitoring fuel levels.
The IoT feature of the DSE891 MKII supports MQTT V 3.1.1 (ISO/IEC 20922:2016). This enables connection to a third party server that is running an MQTT broker, whilst simultaneously supporting connection to the DSEWebNet® server.
The Gateway DSE891 MKII connects to the DSE data server by an integral Ethernet connection only. This is most suited for fixed installations where an ADSL / DSL cable broadband service is available (external broadband modem required, not supplied by DSE).
If you are using the DSE891 MKII as a temporary DSE890 MKII (0890-04) replacement in the EU / EEA markets, please note a third party 4G / 5G IoT Gateway will also be required.
85.5 mm x 136.8 mm x 51 mm (3.36 ” x 5.39 ” x 2.00 ”)
Request a Quote
Product Highlights
Key Features
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 36 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 8 V before dropout and supply recovers to 8 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
200 mA at 12 V
110 mA at 24 V
MAXIMUM STANDBY CURRENT
150 mA at 12 V
90 mA at 24 V
COMMUNICATIONS
USBSingle DSE Controller
CAN (Only active for third-party MQTT brokers)
Multiple DSE Controllers
RS485
Multiple DSE Controllers
Ethernet
Multiple DSE Controllers
Environmental Testing Standards
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment Electrical
SAFETY
BS EN 62368-1
Audio / video, information and communication technology equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 ºC
BS EN 60068-2-2
Bb/Be Dry Heat +70 ºC
BS EN 60068-2-6
Ten sweeps in each of three major axes 5 Hz to 8 Hz at ±7.5 mm, 8 Hz to 500 Hz at 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 ºC at 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 ºC at 93% RH 48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms