Automatic Transfer Switch Control Modules

DSE335 MKII

Auto Transfer Switch Control Module
The DSE335 MKII is an automatic transfer switch controller designed to monitor the voltage and frequency of incoming AC supplies from two different sources. These are either generator or mains (utility), or a combination of both. The module monitors S1 (source 1) and in the event of a failure issues a start command to S2 (source 2). Various timing sequences are available to prevent nuisance starting on minor supply breaks.
The module is configured using the DSE Configuration Suite PC Software. Selected front panel editing is also available. Configurable inputs and outputs make the DSE335 MKII fully flexible to suit a wide variety of applications.
Read More
OVERALL SIZE
240 mm x 181 mm x 42 mm  (9.4” x 7.1” x 1.6”)

PANEL CUT-OUT
220 mm x 160 mm (8.7” x 6.3”) 

MAXIMUM PANEL THICKNESS
8 mm (0.3”)

Request a Quote

e -
Please select a product
Please enter a quantity
e +

add another product

Please enter your title
Please enter your first name
Please enter your surname
Please enter your company name
Please select your country
Please enter a delivery Country/State
Please enter your email
Please enter your mobile number
Webform URL: Website Option: Webform: Named Distributor: Distributor's Email: Named Reseller: Reseller's Email:


l

Product Highlights

Key Features & Benefits

Key Features

Key Benefits

Configurable Inputs (12)
Provides advanced flexibility.
Configurable volt-free outputs (6)
Provides advanced flexibility.
Configurable DC outputs (6)
Provides advanced flexibility.
Single combined switching schemes
Offers simplified programming & operation.
Enhanced configurable closed transition menu (<100 ms)
Provides enhanced accuracy.
415 V AC S1/S2 sensing for full 600 V
Enables the module to fully support 600 volt systems.
Bi-colour front panel LEDs
Offers advanced status indication.
RS485 communications
Provides secure and simple off site monitoring. All ports are continuously active.
4-line back-lit LCD text display
Presents system information clearly.
Five key menu navigation
Ease of use for the operator.
Front panel editing with PIN protection
Protects operators gaining access to the editing functionality without permission.
Check sync feature.
Ensures the smoothest possible transfer is achieved.
Remote monitoring.
Allows operators to view system status from any location.
Source 1/source 2 control.
Allows flexible control of source inputs.
Manual restore to S1.
Allows flexible control of source inputs.
Supports multiple technologies
Offers added flexibility.
Automatic switch-over between supplies
Ensures there is no break in power when the changeover occurs.
Rotary ATS configuration.
Provides alternator breaker type control.
  • Additional Features
  • Configurable timers and alarms
  • Multiple date and time scheduler
  • Power monitoring (kW h, kV Ar, kV A h, kV Ar h)
  • Load switching (load shedding outputs)
  •  
  • USB connectivity
  • Backed up real time clock
  • Fully configurable via DSE
  •  
  • Configuration Suite PC software
  • Configurable display languages
  • Configurable Gencomm pages
  •  
  • DSENet® expansion compatiable
  • Integral PLC editor
  • Adjustable Modbus inter-frame delay
  •  
  • Phase rotation detection
  • Start & load inhibit

Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
 
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
LEDs and backlight will not be maintained during cranking.
 
MAXIMUM OPERATING CURRENT
480 mA at 12 V, 360 mA at 24 V
 
MAXIMUM STANDBY CURRENT
126 mA at 12 V, 96 mA at 24 V

S1

VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS

OUTPUTS A & E
Normally closed ­­­volt-free output
8 A AC at 250 V AC
 
OUTPUTS B & F
Normally open volt-free output
8 A AC at 250 V AC
 
OUTPUT C & D 
Changeover volt-free output
8 A AC at 250 V AC
 
AUXILIARY OUTPUTS G,H,I,J,K & L
2 A DC at supply voltage
­

S2

VOLTAGE RANGE 
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

Environmental Testing Standards

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for 
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for 
the Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, 
including Electrical Business Equipment

TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 °C
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C

VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm, 
8 Hz to 500 Hz @ 2 gn

HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C @ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C @ 93% RH 48 Hours

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.

Connection Diagram

DSE335 MKII connection diagram

Product Variants

No product variants available