Auto Mains (Utility) Failure Control Modules

DSE7420 MKII

Auto Mains (Utility) Failure Control Module
The DSE7420 MKII is an Auto Mains (Utility) Failure Control Module suitable for a wide variety of single, diesel or gas, gen-set applications. Monitoring an extensive number of engine parameters, the modules will display warnings, shutdown and engine status information on the back-lit LCD screen, illuminated LEDs and remote PC. The DSE7420 MKII will also monitor the mains (utility) supply. The module include USB, RS232, RS485 and Ethernet ports as well as dedicated DSENet® terminals for system expansion.

The module is compatible with electronic (CAN) and non-electronic (magnetic pick-up/alternator sensing) engines and offer an extensive number of flexible inputs, outputs and engine protections so the system can be easily adapted to meet the most demanding industry requirements. The comprehensive list of features includes enhanced event and performance monitoring, remote communications & PLC functionality. Dual mutual standby is now available on both the DSE7420 MKII using RS232 or RS485 communications.

The module also feature SNMP functionality for connection to SNMP systems. The module can be easily configured using the DSE Configuration Suite PC software. Selected front panel editing is also available.
OVERALL SIZE
250.0 mm x 189.0 mm x 50.5 mm / 9.85 ” x 7.43 ” x 1.99 ” 

PANEL CUTOUT SIZE
250.0 mm x 189.0 mm / 8.66 " x 6.30 "

MAXIMUM PANEL THICKNESS
8.0 mm / 0.3 ”

PRODUCT VARIANTS
7420-03 

Request a Quote

e -
Please select a product
Please enter a quantity
e +

add another product

Please enter your title
Please enter your first name
Please enter your surname
Please enter your company name
Please select your country
Please enter a delivery County/State
Please enter your email
Please enter your mobile number
Webform URL: Website Option: Webform: Named Distributor: Distributor's Email: Named Reseller: Reseller's Email:


l

Product Highlights

Key Features

Key Features

Advanced PLC functionality including multi-purpose PIDs
Flexible inputs and outputs
DSENet® Expansion Support
PC configuration using DSE Configuration Suite
Multiple language support
Enhanced 4-line text display
Integrated RS232 and RS485 ports providing Modbus RTU support
Integrated Ethernet port providing Modbus TCP, SNMP v2c and in built web SCADA support.
Data logging of up to 20 parameters
Multi-level pin protected front panel editor
Manual front panel and automatic control modes
Latest ECU / ECM support for a wide range of engine manufacturers
IP65 rating (with supplied gasket) offers increased resistance to water ingress
Dual mutual standby between two generators for redundancy and balancing of engine hours
Multiple selectable configurations in one unit to suit changing requirements
Customisable module power-up & screen saver screens
3 phase generator and mains (utility) sensing with protection
Manual starting / control by fascia button and automatic starting / control by inputs and other functions
Automatic start and stopping of generator and transfer of load based on mains (utility) availability
Open and closed transition available with option for synchronisation when used with a CAN engine and DSE CAN AVR

Specification

DC Supply

CONTINUOUS VOLTAGE RATING
8 V to 35 V DC Continuous

CRANKING DROPOUTS
Able to survive 0 V for 100 ms, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. Backlight will not be maintained during cranking

MAXIMUM OPERATING CURRENT

340 mA at 12 V, 160 mA at 24 V

MAXIMUM STANDBY CURRENT
160 mA at 12 V, 80 mA at 24 V

CHARGE ALTERNATOR EXCITATION / FAIL RANGE

0 V to 35 V

Inputs

ANALOGUE INPUTS
Number: 6

Type: Negative Switching Digital Input (6), Resistive Analogue Input (6), Current Analogue Input (4) and Voltage Analogue Input (4)

DIGITAL INPUTS
Number: 8

Type: Negative Switching Digital Input

EMERGENCY STOP INPUT
Number: 1

Type: Positive Switching Digital Input

MAGNETIC PICK-UP INPUT
Voltage Input Range: 0.5 VPeak to 70 VPeak

Frequency Input Range: 5 Hz to 10 kHz

Outputs

DIGITAL OUTPUTS
Number: 10

Type:
1 Normally Open Volt-Free Contacts
1 Normally Closed Volt-Free Contacts
8 Positive Switching DC Output

Environmental Testing Standards

ELECTRO-MAGNETIC  COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.

TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.

HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.

DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.

Connection Diagram

DSE7420 MKII connection diagram

Product Variants

No product variants available