Expansion Modules
DSE2131
DSENet® Ratiometric Input Expansion Module
The DSE2131 DSENet® Ratiometric Input Expansion module is used in conjunction with supported DSENet® modules. The DSE2131 extends the host modules input capabilities for increased application flexibility. This is achieved by providing an additional 10 ratiometric inputs which configured as digital, resistive, 0 V to 10 V or 4 mA to 20 mA.
For enhanced communication with the host module, the DSE2131 features DSENet® for compatible devices. A red status LED is provided to easily identify when the DSE2131 is connected to a power source and communicating with the host controller. The DSE2131 is designed to be mounted within a control panel, either on the panel DIN rail utilising the integral mounts, or chassis mounted utilising the mounting holes.
165 mm x 76 mm x 49 mm (6.5” x 3.0” x 1.9”)
WEIGHT
0.22kg
PRODUCT VARIANTS
2131-01 - 2131 Ratiometric Input Expansion Module
Request a Quote
Product Highlights
Key Features
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8V to 35V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
292 mA at 12 V, 167 mA at 24 V
101 mA at 12 V, 66 mA at 24 V
INPUTS
10 inputs configurable for digital/resistive (3k ohms) 4-20 mA and 0-10 V DC
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
Connection Diagram
Product Variants
2131-01 - 2131 RATIOMETRIC DSENET MODULE