Manual & Auto Start Control Modules
DSE6110 MKIII
Auto Start Control Module
The DSE6110 MKIII is a auto start control module and the DSE6120 MKIII is a auto mains (utility) failure control module suitable for a wide variety of single, diesel or gas, gen-set applications. Monitoring an extensive number of engine parameters, the modules will display warnings, shutdown and engine status information on the back-lit LCD screen.The DSE6120 MKIII will also monitor the mains (utility) supply. The modules include a USB port as well as dedicated DSENet® terminals for system expansion.
Both modules are compatible with electronic (CAN) and non-electronic (magnetic pick-up/alternator sensing) engines and offer an extensive number of flexible inputs, outputs and engine protections so the system can be easily adapted to meet the most demanding industry requirements. The comprehensive list of features includes enhanced event and performance monitoring and PLC functionality. The modules can be easily configured using the DSE Configuration Suite PC software. Selected front panel editing is also available.
221 mm x 163 mm x 42.5 mm / 8.70 ” x 6.43 ” x 1.67 ”
PANEL CUTOUT SIZE
184 mm x 137 mm / 7.24 ” x 5.39 ”
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
Request a Quote
Product Highlights
Key Features
Key Benefits
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
5 V for up to 1 minute
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained
during cranking.
MAXIMUM OPERATING CURRENT
260 mA at 12 V, 150 mA at 24 V
MAXIMUM STANDBY CURRENT
145 mA at 12 V, 85 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
GENERATOR & MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICKUP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
INPUTS
DIGITAL INPUTS A to H
Negative switching
ANALOGUE INPUTS A & D
Configurable as:
Negative switching digital input
0 V to 10 V sensor
4 mA to 20 mA sensor
Resistive sensor
ANALOGUE INPUTS B & C
Configurable as:
Negative switching digital input
Resistive sensor
OUTPUTS
OUTPUT A & B (FUEL & START)10 A DC at supply voltage
AUXILIARY OUTPUTS C, D, E, F, G & H
2 A DC at supply voltage
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.