Load Sharing & Synchronising Control Modules

DSE8620 MKII

Synchronising Auto Mains (Utility) Failure Load Share Control Module
The DSE8620 MKII represents the latest in complex load sharing & synchronising control technology. Designed to synchronise a single genset with a mains (utility) supply, the DSE8620 MKII control module is packed with multiple features and benefits that are unrivalled across the generator control industry.

The controller also has the option to be configured for use as a DSE8610 MKII Auto Start Load Sharing & Synchronising Control Module. When converted for use as a DSE8610 MKII the unit provides generator to generator load share functionality. 

To view UL Certification click here.

OVERALL SIZE
245 mm x 184 mm x 51 mm (9.6" x 7.2" x 2.0")

PANEL CUTOUT SIZE
220 mm x 160 mm (8.7" x 6.3")

MAXIMUM PANEL THICKNESS
8.0 mm (0.3")

WEIGHT
0.88kg

PRODUCT VARIANTS
8620-02 - 8620 MKII Synchronising Auto Mains (Utility) Failure Load Sharing Control Module

Request a Quote

e -
Please select a product
Please enter a quantity
e +

add another product

Please enter your title
Please enter your first name
Please enter your surname
Please enter your company name
Please select your country
Please enter a delivery Country/State
Please enter your email
Please enter your mobile number
Webform URL: Website Option: Webform: Named Distributor: Distributor's Email: Named Reseller: Reseller's Email:


l

Product Highlights

Key Features & Benefits

Key Features

Key Benefits

Refer to product data sheet for complete list of integrated features.
Extended PLC function types.
Provides ultimate flexibility for complex grid type generator installations.
Redundant MSC.
Allows two MSC links to be connected between multiple DSE86xx MKII control modules.
Type 1 fully flexible inputs.
Flexible for configuration as voltage, current or resistive.
Two RS485 ports.
Aids communication with electronic engines and building management systems.
Three CAN ports.
Ultimate CAN flexibility. Connect to DSENet devices, communicate with electronic engines and maintain a redundant MSC link.
32-set synchronisation.
Offers optimum flexibility for system expansion.
Configurable inputs/outputs (12/8).
Provides multiple installation options.
Dead bus sensing.
Provides rapid power delivery on multi-set systems.
Remote communications (RS232, RS485, Ethernet).
Provides secure and simple off site monitoring. All ports are continuously active.
Direct governor control.
Eliminates the requirement for external control equipment.
kW & kV Ar load sharing.
Provides controlled power delivery.
Configurable event log (250).
Provides access to historical alarms and operational status.
Load switching, load shedding & dummy load outputs.
Allows load options and dummy load requirements to be independently controlled.
Power monitoring (kW h, kVAr, kv Ah, kV Ar h), reverse power protection, kW overload protection.
Provides clear accurate power measurement information.
Data logging (USB Memory Stick).
Provides current and historical status information.
DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Tier 4F Stage V CAN engine support.
Ensures the control module can be used with the latest in modern electronic engine technology.
Sophisticated emission control with DPF regeneration & soot capture.
When soot loading in the filters reaches a set limit the control module can control the regeneration to lower soot levels in the DPF.
Separate ramp up and ramp down rates configurable via PLC.
Enables different values to be configured.
In-built SNMP.
Provides additional flexibility.
Battery charger support across DSENet®.
View connected charger information on the display of the control module.
Configurable CAN transmit and receive.
Provides additional flexibility.
Sophisticated data logging.
Provides detailed site data for detailed analysis.
Support for 0-10 V & 4-20mA sensors.
On-board analogue input supports 3rd party equipment as standard.
Can be configured for use as a DSE8610 MKII.
Provides flexibility to the end user.
Can be used as a rear mounted solution using a DSE rear mount panel bracket.
Gives flexibility to use the product in the front or rear of a panel.

Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING
5 V to 35 V continuous

CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries

MAXIMUM OPERATING CURRENT
530 mA at 12 V, 280 mA at 24 V

MAXIMUM STANDBY CURRENT
320 mA at 12 V, 160 mA at 24 V

CHARGE FAIL/EXCITATION RANGE
0 V to 35 V

OUTPUTS

OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A AC at 250 V AC (Volt free)

AUXILIARY OUTPUTS E to L
2 A DC at supply voltage

GENERATOR & BUS

VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V

FREQUENCY RANGE
10,000 Hz (max)

BUILT-IN GOVERNOR CONTROL

MINIMUM LOAD IMPEDANCE
500Ω
Fully isolated

GAIN VOLTAGE
0 V to 10 V DC
Fully isolated

OFFSET VOLTAGE
0 V to 10 V DC
Fully isolated

BUILT-IN AVR CONTROL

MINIMUM LOAD IMPEDANCE
500Ω
Fully isolated

GAIN VOLTAGE
0 V to 10 V DC
Fully isolated

OFFSET VOLTAGE
+/- 10 V DC
Fully isolated

Environmental Testing Standards

ELECTRO-MAGNETIC  COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.

TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.

HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.

DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.

Connection Diagram

DSE8620 MKII connection diagram

Product Variants

No product variants available