Expansion Modules
DSE2170
DSENet® RTD / Thermocouple Input & Analogue Output Expansion Module
120 mm x 75 mm x 31.5 mm / 4.72 ” x 2.95 ” x 1.24 ”
MOUNTING
DIN Rail: 35 mm / 1.35”
Chassis: 2 M4 mounting holes with 108 mm x 63 mm / 4.25” x 2.48” centres
PRODUCT VARIANTS
2170-01
Request a Quote
Product Highlights
Key Features
Specification
DC Supply
CONTINUOUS VOLTAGE RATING8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 ms, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs are not maintained during cranking.
MAXIMUM OPERATING CURRENT
200 mA at 12 V, 95 mA at 24 V
MAXIMUM STANDBY CURRENT
50 mA (no communication active)
Inputs / Outputs
RTD / THERMOCOUPLE INPUTSNumber: 4
Type: J Type Thermocouple, K Type Thermocouple, L Type Thermocouple, Pt100 or Pt1000
ANALOGUE OUTPUTS
Number: 4
Type: 0 V to 10 V or 0 mA to 20mA
Communications
DSENet®Fully Isolated
CAN
Fully Isolated
Environmental Testing Standards
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
Electrical Safety
BS EN 61010
Safety of Information Technology Equipment, including Electrical Business Equipment
Temperature
BS EN 60068-2-1
Ab/Ae Cold Test -30°C
BS EN 60068-2-2
Bb/Be Dry Heat +70°C
Vibration
BS EN 60068-2-6
Ten sweeps in each of three major axes
5Hz to 8 Hz at ±7.5mm
8Hz to 500 Hz at 2Gn
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55°C at 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40°C at 93% RH 48 Hours
Shock
BS EN 60068-2-27
Three shocks in each of three major axes
15 Gn in 11 ms
Degrees of Protection Provided by Enclosures
BS EN 60529
IP21