Intelligent Battery Chargers
DSE9474
24 Volt 30 Amp Intelligent Battery Charger
The DSE9474 is an intelligent 24 volt, 30 amp switched-mode battery charger that has fully programmable charging curves, making it suitable for multiple different battery chemistry types. The battery charger is programmed using the DSE Configuration Suite PC Software and is mounted direct to a chassis for ease of integration and installation. There are also three integrated LEDs mounted to the battery charger to indicate current charging status and fault conditions.
The battery charger has no moving parts, delivering additional durability and reliability, and continues to operate when the engine is running.
240 mm x 263 mm x 89 mm / 9.45 ” x 10.35 ” x 3.05 ”
WEIGHT
2.5kg / 5 lb 8.18 oz
Request a Quote
Product Highlights
Key Features
Specification
AC SUPPLY
Minimum Supply Voltage
90 VAC with Charge Output De-rate
110 VAC without Charge Output De-rate
Maximum Supply Voltage
305 VAC
Frequency Range
48 Hz to 64 Hz
Maximum Operating Current
9.0 AAC at 110 VAC, 4.0 AAC 230 VAC
CHARGE OUTPUT
Voltage Range
26 VDC to 31 VDC
Voltage Ripple and Noise
1 % of Configured Boost Voltage
Voltage Load Regulation
1 %
Voltage Line Regulation
Less than 0.01 % Requested Charge Output Voltage
DIGITAL INPUT
Number
1
Type
Contact Between Terminals
Closed Voltage Threshold
Less than 2.1 V
Open Voltage Threshold
Greater than 6.6 V
TEMPERATURE SENSOR INPUT
Number1
Type
PT1000
CHARGE FAIL OUTPUT
Number
1
Type
Normally Closed Volt-Free Contact
Volt-Free Contact Output Rating
3 ADC resistive at 30 VDC
Environmental Testing Standards
Electro-Magnetic Compatibility
BS EN 61000-6-2EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
Temperature
BS EN 60068-2-1Ab/Ae Cold Test -30 ºC
BS EN 60068-2-2
Bb/Be Dry Heat +70 ºC
Vibration
BS EN 60068-2-6Ten sweeps in each of three major axes
5 Hz to 8 Hz at ±7.5 mm
8 Hz to 500 Hz at 2 Gn
Humidity
BS EN 60068-2-30Db Damp Heat Cyclic 20/55 ºC at 95% Relative Humidity 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 ºC at 93% Relative Humidity 48 Hours
Shock
BS EN 60068-2-27Three shocks in each of three major axes 15 Gn in 11 ms
Degrees of Protection Provided by Enclosures
BS EN 60529IP21
Connection Diagram