Digital Automatic Voltage Regulators (AVR)

DSEA109

Digital Automatic Voltage Regulator (AVR) with CAN Communications & PMG Support

The DSEA109 Digital Automatic Voltage Regulator (AVR) is designed to regulate the output voltage of an AC generator. The DSEA109 is supplied by either a Permanent Magnet Generator (PMG), stator auxiliary winding or self excited from the generator’s main stator windings (shunt).

The DSEA109 eliminates the complexities involved with analogue AVR designs. Analogue AVR designs can be oversensitive to change in temperature which affects the generators output voltage stability, where as the DSEA109 AVR maintains a smooth, stable regulated AC output voltage, regardless of the electrical load connected. The DSEA109 also features 3 phase generator terminal sensing for better regulation.

The DSEA109 is simple to install and set up using the DSE Configuration Suite PC Software with the DSE815 configuration interface. On board DIP switches and potentiometers can be used to further adjust the selected configuration and set points within the AVR at a later date by on site maintenance engineers.

The DSEA109 has numerous advanced features such as a CAN port providing J1939 communications. This allows the AVR to be connected to supported DSE modules to display AVR instrumentation, and send control commands such as voltage adjustment and configuration selection. In addition to this, the DSEA109 also provides a soft start ramping feature, connection for a droop CT and the ability to perform remote voltage set point adjustment. All of these feature make it perfect for synchronising and loadsharing applications.

The DSEA109 AVR is an ideal option for both OEM and retro-fit solutions and is a suitable aftermarket replacement for multiple OEM AVR products.

Speak to DSE’s dedicated Technical Support team before placing your order to confirm full compatibility.

Read More
OVERALL SIZE
180 mm x 145 mm x 61 mm (7.09 ” x 4.72 ” x 2.40 ”) 

WEIGHT
0.62 kg / 1.37 lb

PRODUCT VARIANTS
A109-01

Request a Quote

e -
Please select a product
Please enter a quantity
e +

add another product

Please enter your title
Please enter your first name
Please enter your surname
Please enter your company name
Please select your country
Please enter a delivery County/State
Please enter your email
Please enter your mobile number
Webform URL: Website Option: Webform: Named Distributor: Distributor's Email: Named Reseller: Reseller's Email:


l

Product Highlights

Key Features

Key Features

LED Indication for fault and operating status.
On board DIP switch selection for 6 configurations and 2 stability ranges
On board potentiometer adjustment for generator voltage set point
On board potentiometer adjustment for droop percentage
On board potentiometer adjustment for UFRO start frequency
On board potentiometer adjustment for proportional (gain) and integral (stability)
Remote generator voltage set point adjustment
Compatible with single phase and 3 phase power supply source
Single or 3 phase generator terminal voltage sensing
Loss of generator terminal voltage sensing
Under Frequency Roll Off (UFRO) protection with optional instantaneous step
Over excitation protection.
Optional idle running detection to prevent over excitation
Soft ramping of generator terminal voltage to set point on start up
CAN port providing J1939 communication allowing compatible DSE modules to display AVR instrumentation and send control commands for voltage control and stability / configuration selection

Specification

Power Supply

SUPPLY SOURCE
Self Excited (Shunt), Auxiliary Winding or PMG

SUPPLY INPUT
Single Phase or 3 Phase

VOLTAGE RANGE
100 V AC to 270 V AC

FREQUENCY RANGE
40 Hz to 400 Hz

Generator Terminal Voltage Measurement

MEASUREMENT INPUT
Single Phase or 3 Phase

VOLTAGE RANGE
15 V AC to 600 V AC

VOLTAGE ACCURACY
±0.5 %

FREQUENCY RANGE
40 Hz to 65 Hz

FREQUENCY ACCURACY
±0.2 Hz

Excitation Output

VOLTAGE RANGE
0 V DC to 100 V DC continuous

100 V DC to 150 V DC for 10 seconds

CURRENT RANGE
0 A DC to 7 A DC continuous

7 A DC to 15 A DC for 10 seconds

MAXIMUM CONTINUOUS OUTPUT POWER
500 W

EXCITER WINDING IMPEDANCE
5 Ω to 50 Ω

EXCITER WINDING INDUCTANCE
0.3 H to 1.2 H

Droop CT Current Measurement

MEASUREMENT INPUT
Single Phase

CURRENT RANGE
0 A to 5 A

VA RATING
0.25 VA

ACCURACY
±0.05 A

DROOP ADJUSTMENT
0 % to 10 %

Remote Bias Inputs

NUMBER
2

TYPE
1 Resistive Analogue Input

1 Voltage Analogue Input

RESISTIVE ANALOGUE INPUT RANGE
0 Ω to 5 kΩ

RESISTIVE BIAS RANGE
±1 % to ±16 % of Nominal Voltage

VOLTAGE ANALOGUE INPUT RANGE
-10 VDC to +10 VDC

VOLTAGE ANALOGUE INPUT IMPEDANCE
Greater than 10 kΩ

VOLTAGE BIAS RANGE
±1 %/V to ±16 %/V of Nominal Voltage

Environmental Testing Standards

ELECTRO-MAGNETIC  COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.

TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.

HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.

Product Variants