Expansion Modules
DSE157
Output Relay Expansion Module
The DSE157 is an output relay expansion module designed for use with the DSE 52xx, 53xx and 55xx control modules.
The module includes eight configurable relay contacts (energised/de-energised) that enable Original Equipment Manufacturers (OEMs) to achieve greater output flexibility to meet complex industry generator control specifications.
OVERALL SIZE
72 mm x 160 mm x 77 mm (2.8” x 6.3” x 3.0”)
Request a Quote
Product Highlights
Key Features
Specification
DC SUPPLY
The DSE157 is powered from the plant battery or from a low voltage supply between 8V and 35V continuous. It is able to survive 0V for 50ms during cranking, providing supply was at least 10V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries.MAXIMUM OPERATING CURRENT
120mA @ 12V, 70mA @ 24V
MAXIMUM STANDBY CURRENT
25mA @ 12V, 18mA @ 24V
AUXILIARY RELAY CONTACTS
5Amp DC rated voltage free
SELECTOR SWITCHES
Test - Operates all relays to test operation.Unused - No function.
Enable Lamp Test - Relays will energise on receipt of a lamp test signal from host module.
A/B Select - Determines whether the DSE157 responds to signals for expansion A or B relays.
INDICATIONS
Lit LED - Power OnFlashing LED - Link lost (to controller)
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
Connection Diagram