Manual & Auto Start Control Modules
DSE3110
Manual & Auto Start Control Module
99 mm x 79 mm x 41.5 mm / 3.9” x 3.11” x 1.63”
Panel Cut-Out (W x H)
80 mm x 68 mm / 3.15” x 2.86”
Maximum Panel Thickness
8 mm / 0.31”
Request a Quote
Product Highlights
Key Features
Specification
DC Supply
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. Backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
76 mA at 12 V, 61 mA at 24 V
MAXIMUM STANDBY CURRENT
45 mA at 12 V, 43 mA at 24 V
CHARGE ALTERNATOR EXCITATION / FAIL RANGE
8 V to 35 V fixed power source 2.5 W
Inputs
DIGITAL
Number: 6
Type: Negative Switching
EMERGENCY STOP
Number: 1
Type: Negative Switching
MAGNETIC PICK-UP
Voltage Input Range: 0.5 VPeak to 70 VPeak
Frequency Input Range: 5 Hz to 10 kHz
Outputs
DIGITAL
Number: 4
Type: Positive Switching
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 61010
Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory
use.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 Gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 - From the front of the module when installed into a control panel (with optional gasket)
Connection Diagram