Manual & Auto Start Control Modules
DSE3110
Manual & Auto Start Control Module
The DSE3110 includes a back-lit icon LCD display which clearly shows the status of the generator set at all times. The module monitors engine speed, frequency, voltage and engine run hours and also displays the warning and shutdown status.
The module includes fixed and configurable outputs as well as configurable inputs making this product ideal for a wide variety of applications. The module can either be programmed using the front panel or by using the DSE Configuration Suite PC software.
99 mm x 79 mm x 41.5 mm / 3.9” x 3.11” x 1.63”
PANEL CUTOUT SIZE
80 mm x 68 mm / 3.1 " x 2.7"
MAXIMUM PANEL THICKNESS
8.0 mm / 0.3”
Request a Quote
Product Highlights
Key Features
Specification
DC Supply
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. Backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
76 mA at 12 V, 61 mA at 24 V
MAXIMUM STANDBY CURRENT
45 mA at 12 V, 43 mA at 24 V
CHARGE ALTERNATOR EXCITATION / FAIL RANGE
8 V to 35 V fixed power source 2.5 W
Inputs
DIGITAL
Number: 6
Type: Negative Switching
EMERGENCY STOP
Number: 1
Type: Negative Switching
MAGNETIC PICK-UP
Voltage Input Range: 0.5 VPeak to 70 VPeak
Frequency Input Range: 5 Hz to 10 kHz
Outputs
DIGITAL
Number: 4
Type: Positive Switching
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 61010
Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory
use.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 Gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
BS EN 60529
IP65 - From the front of the module when installed into a control panel (with optional gasket)
Connection Diagram