Auto Mains (Utility) Failure Control Modules

DSE720

Auto Mains (Utility) Failure Control Module
The DSE720 is an Automatic Mains (Utility) Failure Control Module suitable for a wide variety of single diesel or gas genset applications. Monitoring an advanced list of engine parameters, the DSE720 will automatically shut down the engine or indicate a warning, on detection of a fault condition. The fault is indicated on the module’s front panel LCD display or LED. The module can be easly configured using the DSE810 interface and PC Software. The module can be controlled from a PC that is located up to a maximum distance of 100 meters away. Front panel editing is also available.
 The DSE720 also has the ability to monitor the mains (utility) supply, automatically controlling the switch-over to generator when the mains (utility) power fails.
Read More

Request a Quote

e -
Please select a product
Please enter a quantity
e +

add another product

Please enter your title
Please enter your first name
Please enter your surname
Please enter your company name
Please select your country
Please enter a delivery Country/State
Please enter your email
Please enter your mobile number
Webform URL: Website Option: Webform: Named Distributor: Distributor's Email: Named Reseller: Reseller's Email:


l

Product Highlights

Key Features

Key Features

Specification

Environmental Testing Standards

ELECTRO-MAGNETIC  COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.

TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.

VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.

HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.

DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.

Product Variants

No product variants available